AXD Micromanometers
 |
|
AXD560/AXD540
* Meter shown with optional
accessory probe
|
Alnor
AXD Micromanometers are used by test and balance professionals,
contractors and facilities engineers to measure pressure, velocity,
or volume in general industrial applications. The AXD 540 Micromanometer
is ideal for taking velocity traverses in ductwork and for verifying
the accuracy of installed gauges. The AXD 560 is an high-performance
instrument for HVAC professionals who need fast, accurate pressure
or volume, or velocity measurements combined with advanced calculation
and data logging capabilities.
All AXD Micromanometers measure pressure, calculate velocity when
used with a pitot probe, calculate averages of pressure or velocity
readings, and have one-key zeroing to ensure the accuracy of your
readings. You can print your readings when using the optional MicroPrinter
Portable Printer.
The AXD 560 includes better resolution, advanced calculations, and
data logging abilities. It calculates volume automatically when
a duct size and shape is entered, and stores up to five different
K factors for use when measuring volume. This model also converts
between actual and standard velocity or volume readings, stores
up to 1000 samples of pressure, velocity, or volume, and calculates
statistics for the stored samples. All stored data can be reviewed
on the instrument display or downloaded to a computer spreadsheet
using the supplied Alnor downloading software.
Both the AXD 540 and the AXD 560 are available alone or as kits
containing the accessories needed to make a variety of pressure,
velocity, and volume measurements. |
| |
AXD
560
|
AXD
540
|
| range |
pressure |
-5 to 15 in. H2O (-1245 to 3735
Pa) |
-5 to 15 in. H2O (-1245 to 3735
Pa) |
| |
velocity |
250 to 15,500 ft/min (1.27 to 78.7
m/s) |
250 to 15,500 ft/min (1.27 to 78.7
m/s) |
| |
volume |
up to 9,999,000 cfm, m3/h, l/s |
NA |
| accuracy |
±1% of reading ±0.005 in. H2O (±1% of reading ±1
Pa) |
±1% of reading ±0.005 in. H2O (±1% of reading ±1
Pa) |
| resolution |
0.0005 in. H2O (0.1 Pa) |
0.001 in. H2O (1 Pa) |
| data storage |
1000 samples |
NA |
| power source |
four AA-size alkaline batteries |
four AA-size alkaline batteries |
| battery life |
typical 40 hours |
typical 40 hours |
|